Powercom UPS Australia
Vanguard II 1500VA PSW On-Line, L Series*
$2,000.00
AUD
inc. GST
On-Line Double Conversion, Industrial Pure Sine Wave (PSW), 0.9pf. Tower Style GPO Aus 3pin Outlets
LCD Front Panel, Network/Alarm Card Slot, External Battery Pack Connector and USB Interface.
UPS
Model
VGS-1500L
Capacity VA
1500
Capacity (Watts)
1350
Form
Tower
Phase
Single Phase
Energy Saving
Yes - ECO mode Efficiency > 94%
INPUT
Voltage
220 / 230 / 240 Vac
Voltage Range
120 ~ 276 Vac < 25% Load
140 ~ 276 Vac < 50% Load
160 ~ 276 Vac < 75% Load
180 ~ 276 Vac < 100% Load
Frequency Range
50 / 60Hz ±2.5Hz auto sensing (45 to 65Hz user selectable)
Power Factor
> 0.97
Cold Start
Yes
OUTPUT
Rated Power Factor
0.9
Waveform
Pure Sine Wave
Voltage
208 / 220 / 230 / 240 Vac ±2% (selectable output voltage)
Frequency
50 / 60 Hz ±0.25 Hz
Transfer Time
0 ms
Harmonic Distortion
< 5% of T.H.D. at non-Linear Load | < 2.5% of T.H.D. at Linear Load
Crest Factor
3 : 1
EPO Function
Yes
Efficiency
Approximately 89%
Connections
*Please refer below "Receptacle Options"
Customized receptacle can be discussed
PROTECTION
Overload
Line Mode
106% - 120% for 30 seconds
121% - 150% for 10 seconds
Overload
Battery Mode
101% - 109% for 10 seconds
110% - 120% for 3 seconds
Tele-Communication
RJ45 x 2
Surge Protection
IEC 61000-4-5 Level 3
Bypass
Internal Bypass(Automatic and Manual)
Short Circuit Protection
UPS output cut off immediately or protected by input fuse or circuit breaker
Alarm
Buzzer beeps under backup mode, battery low, battery charging fault, and overload
Overload Protection
UPS automatic power off if overload exceeds 106% to 120% of nominal at 30 seconds;
121% to 150% for 10 seconds;
CHARGER
UPS
1A
UPS Build In
5A
Total
6A
BATTERY
Model
VGS-1500-L
DC Voltage
48V
MANAGEMENT
Indicator
LCD/LED Control Panel
Communication Port
RS232, USB(B-type)
SNMP Slot
Option
Audible Alarms
YES
PHYSICAL
Dimension (W×D×H)(mm)
152 x 500 x 241
Weight (kgs)
10.1
Shipping Dimensions (mm)
280 x 625 x 356
Shipping Weight (kgs)
12